Space heating used 32% of the energy in US commercial buildings in 2018, according to the EIA’s latest building survey. Most of those buildings need more than one kind of heater. A warehouse floor, a front entry and a row of offices lose heat in different ways. Pick the heater for each space first, then the fuel the building already has.
| Space | Heater that usually fits | Watch for |
| Open warehouse or shop floor | Gas unit heater | Vent path and gas line size |
| Shop with dust, dirt or humidity | Separated combustion gas unit heater | An air intake as well as the vent |
| Large open or semi-enclosed area | Infrared heater | Tall racks block the heat |
| Entry, hallway or stairwell | Cabinet unit heater or electric wall heater | Hot water supply or electrical capacity |
| Offices and walls under windows | Baseboard, fin tube or convectors | Boiler water or a circuit |
| Electrical room or small add-on | Electric unit heater | Running cost if it runs all day |
| Building with a working boiler | Hydronic unit heater | Spare boiler capacity |
Gas unit heaters for open floors
A gas unit heater hangs from the ceiling and blows warm air down to the floor. It suits warehouses, shops and service bays with natural gas or propane on site.
A standard unit takes combustion air from the room. A separated combustion unit pulls its air from outside, which suits spaces with dust, dirt or humidity. Modine, for one, builds its separated combustion line for those shops.
Best for: large open space with gas service. Falls short: tall ceilings, where warm air pools at the roof.
Infrared heaters for large and semi-enclosed spaces
An infrared heater warms people, floors and equipment directly instead of heating the air. Gas models run on natural gas or propane, and electric models are also made.
“Infrared works best when the heater can see the people it’s heating,” said Ed Heinlein, VP of Heinlein Supply. “Fill the floor with racks over 12 feet and the heat lands on the top shelf. We look at the rack layout before we recommend it for a warehouse.”
Best for: spot heating and large open or semi-enclosed areas. Falls short: warehouse floors packed with tall racks.
Electric heaters for small spaces
An electric unit heater needs power and a place to hang, with no gas line and no flue. That makes it the easy answer for electrical rooms, guard shacks and small add-ons. Explosion-proof and washdown models cover hazardous or wet rooms.
Best for: small zones with no gas service. Falls short: a whole warehouse, where the power bill adds up fast.
Hydronic heaters when the building has a boiler
A hydronic unit heater runs on hot water or steam from an existing boiler. A fan blows air across a coil, so there is no burner in the room. If an older building already has a boiler loop, a renovation can reuse it.
Best for: renovations that keep a working boiler. Falls short: buildings with no boiler, or no spare boiler capacity.
Baseboard, convectors and cabinet heaters for offices and entries
Baseboard heat runs along an outside wall, usually under windows, with no fan noise. Electric baseboard needs only a circuit. Hydronic baseboard, called fin tube, runs on boiler water. Convectors do the same job inside a cabinet. Cabinet unit heaters add a fan and suit hallways, entries and lobbies.
Best for: offices, classrooms and front entries. Falls short: open floors and high ceilings.
How to compare gas and electric running costs
One therm of gas holds 100,000 BTU. One kWh holds 3,412 BTU, so about 29.3 kWh match a therm (EIA).
At August 2026 US commercial averages from the EIA, gas cost $12.87 per thousand cubic feet. That is about $1.24 a therm, or about $1.55 delivered through an 80% efficient heater. Electricity cost 14.47 cents per kWh, so the same heat costs about $4.24. Electric ran nearly three times higher. Rates vary by state, so check your own bills.
Four mistakes on commercial renovations
- Heating the ceiling. In one DOE warehouse test, ceiling air ran 10 to 20°F above the thermostat setting. Destratification fans push that heat back down.
- Forgetting combustion air. New insulation and sealed doors cut the air standard gas heaters burn. Separated combustion solves it.
- Replacing what a part could fix. Depending on the unit, a failed motor or control may be a simple swap. For Modine heaters, look up Modine heater parts by the unit model number.
- Ignoring the dock doors. PNNL’s warehouse model assumes 783 cfm of outside air per open dock door.
“Over half the calls we get about a dock heater that can’t keep up turn out to be a door problem,” Heinlein said. “The door is open half the shift, or the seals are torn. Fix the door first, then size the heater.”
Most buildings end up with three or four heater types under one roof. A distributor such as Heinlein Supply can match the heater to the room and your fuel.
FAQ
Is infrared or a unit heater better for a warehouse?
Gas unit heaters suit most warehouses with gas service. Infrared heaters warm people and objects directly, so less of the heat depends on air that rises to the roof.
Is hydronic heating gas or electric?
Hydronic heating moves heat with hot water or steam. The boiler can burn natural gas, propane or oil, or run on electricity, according to the DOE.
Can a renovation swap gas unit heaters for electric?
A renovation can swap gas unit heaters for electric if the electrical service can handle the load. Check panel capacity and compare utility rates first.
About the author: Ed Heinlein is Vice President of Heinlein Supply, the authorized Modine and Loren Cook rep in Chicago.